Input
type of the power supply network Controlled DC voltage
supply voltage at DC rated value 24 V
input voltage at DC 22 … 30 V
overvoltage overload capability 35 V
input current at rated input voltage 24 V rated value 40 A
Output
voltage curve at output controlled DC voltage
formula for output voltage Vin – approx. 0.2 V
relative overall tolerance of the voltage note In accordance with the supplying input voltage
number of outputs 4
output current up to 60 °C per output rated value 10 A
adjustable current response value current of the currentdependent overload release
3 … 10 A
type of response value setting via potentiometer
product feature parallel switching of outputs No
type of outputs connection Simultaneous connection of all outputs after power up of the supply voltage >
20 V, delay time of 25 ms, 100 ms or adjustable “load optimised” via DIP switch
for sequential connection
Efficiency
efficiency in percent 99 %
power loss [W] at rated output voltage for rated value of the
output current typical
10 W
Switch-off characteristic per output
switching characteristic
● of the excess current Iout = 1.0 …1.5 x set value, switch-off after approx. 5 s
● of the current limitation Iout = 1.5 x set value, switch-off after typ. 100 ms
● of the immediate switch-off Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
residual current at switch-off typical 1 mA
design of the reset device/resetting mechanism via sensor per output
remote reset function Non-electrically isolated 24 V input (signal level “high” at > 15 V)
Protection and monitoring
fuse protection type at input 15 A per output (not accessible)
display version for normal operation Three-color LED per output: green LED for “Output switched through”; yellow
LED for “Output switched off manually”; red LED for “Output switched off due to
overcurrent”
design of the switching contact for signaling function Common signal contact (changeover contact, rating 0.1 A/24 V DC)
Safety
galvanic isolation between input and output at switch-off No
standard for safety according to EN 60950-1 and EN 50178
operating resource protection class Class III